Florida AHJ

Solar permit requirements in Un-incorporated Palm Beach, FL

Solar projects in Un-incorporated Palm Beach must adhere to specific structural and electrical standards. Solar Design Lab provides permit-ready plansets that comply with these local regulations.

Requirements at a glance

Design wind speed
170 mph (ASCE)
Exposure category
B
Ground snow load
0 psf
High-velocity hurricane zone
No
Submission format
digital_separate
Separate discipline files
Yes

What Un-incorporated Palm Beach expects on a solar permit

Permit applications require digital submission with separate discipline files. Structural designs must account for a wind speed of 170 mph, Exposure B, and Risk Category II per FBC 2023 and ASCE 7-22. Documentation must include electrical and structural certifications by a Florida-licensed PE referencing Florida Statute 377.705. Additional requirements include a 36-inch ridge setback if PV arrays occupy more than 33 percent of the roof area and the use of reflective PV system labels with 3/8 inch lettering. Electrical specifications require a service-entrance rated PV AC disconnect for supply side connections and a 200A rated MSP with a 200A main breaker for Tier 2 systems. Installations must also include 10-year non-removable battery-operated smoke alarms in sleeping rooms and adjacent areas.

  • [structural] Design structures for a wind speed of 170 mph, Exposure B, and Risk Category II per FBC 2023 and ASCE 7-22.
  • [labeling] Use reflective PV system labels with a minimum letter height of 3/8 inch per NFPA 1-11.12.2.1.1.2.
  • [calcs] Calculate EV charger loads at 100% in the electrical load calculations.
  • [fire] Provide a minimum 36-inch ridge setback if PV arrays occupy more than 33 percent of the plan view roof area.
  • [documentation] Include electrical and structural certifications by a Florida-licensed PE referencing Florida Statute 377.705.
  • [electrical] Specify a service-entrance rated PV AC disconnect if connected to the supply side of the service.
  • [electrical] Specify a 200A rated Main Service Panel (MSP) with a 200A main breaker for Tier 2 solar systems.
  • [fire] Specify 10-year non-removable, non-replaceable battery-operated smoke alarms in sleeping rooms and adjacent areas.